Sl. No. |
Desc. |
Material |
Surface Treatment |
Qty. |
|
1 |
Top Metal Fitting |
SGCI |
H.D.G. |
1 |
|
2 |
Core Rod |
Fibreglass |
- |
1 |
|
3 |
Polymer Housing |
Silicon Rubber |
- |
- |
|
4 |
Bottom Metal Fitting |
SGCI |
H.D.G. |
1 |
|
5 |
Stud |
M.S. |
M22 |
1 |
|
6 |
Plain Washer |
M.S. |
M22 |
1 |
|
7 |
Nut |
M.S. |
M22 |
1 |
|
8 |
Lock Nut |
M.S. |
M22 |
1 |
Guaranteed technical particulars :
Dimensions :
-
Minimum creepage distance mm 610
-
Arcing distance (approx.) mm 250
-
Ø250mm sheds nos 2
-
Ø175mm sheds nos 2
Mechanical Characteristic
:
-
Specified cantilever load kN 11
Electrical Characteristics
:
-
Nominal system voltage kV 20
-
Highest system voltage kV 24
-
System frequency hz 50
-
Wet 1 minute power frequency withstand voltage
kV (rms.) 50
-
Dry lightening impulse withstand kVp
145
-
Visible discharge test voltage kV(rms)
18
Applicable Standard :
-
Insulator : IEC 61109-2008
-
Galvanization : IS 2633-1986